Description
Details
| 220V 3ph rated voltage( adapt to the working voltage range 208~240V ±15%) | ||||||||||
| Model 220V | Rated Value | General Load Application | Heavy Load Application | Noise Level | Heat Radiation | Air Volume | SKU | |||
| In( A) | Imax(A) | ILd( A) | PLd(kW) | IHd( A) | PHd(kW) | dBA | w | m3/h | ||
| ES580-01-0K4G/0K7P-2B | 5.2 | 7 | 5 | 0.75 | 2.5 | 0.37 | 45 | 40 | 89 | 1210001 |
| ES580-01-0K7G/1K5P-2B | 6.3 | 9 | 6 | 1.5 | 4.2 | 0.75 | 45 | 76 | 89 | 1210002 |
| ES580-01-1K5G/2K2P-2B | 10.5 | 15 | 9.8 | 2.2 | 5.6 | 1.5 | 45 | 97 | 89 | 1210003 |
| ES580-01-2K2G/4K0P-2B | 18.2 | 25 | 17.5 | 4 | 14.5 | 2.2 | 45 | 172 | 130 | 1210004 |
| ES580-02-4K0G/5K5P-2B | 26 | 36 | 25 | 5.5 | 17.6 | 4 | 45 | 325 | 130 | 1210005 |
| ES580-02A-5K5G/7K5P-2B | 37 | 50 | 35 | 7.5 | 25 | 5.5 | 52 | 470 | 175 | 1210006 |
| Model 380V | 380V 3ph rated voltage ( adapt to the working voltage range 380~460V ±15%) | |||||||||
| ES580-01-0K7G/1K5P-3B | 5.2 | 7 | 5 | 1.5 | 2.5 | 0.75 | 45 | 40 | 89 | 1210011 |
| ES580-01-1K5G/2K2P-3B | 6.3 | 9 | 6 | 2.2 | 4.2 | 1.5 | 45 | 76 | 89 | 1210012 |
| ES580-01-2K2G/4K0P-3B | 10.5 | 15 | 9.8 | 4 | 5.6 | 2.2 | 45 | 97 | 89 | 1210013 |
| ES580-01-4K0G/5K5P-3B | 14 | 20 | 13.5 | 5.5 | 10.5 | 4 | 45 | 172 | 89 | 1210014 |
| ES580-01-5K5G/7K5P-3B | 18.2 | 25 | 17.5 | 7.5 | 14.5 | 5.5 | 45 | 210 | 130 | 1210015 |
| ES580-02-7K5G/011P-3B | 26 | 36 | 25 | 11 | 17.6 | 7.5 | 45 | 325 | 130 | 1210016 |
| ES580-02-011G-3B | 28 | 35 | 26 | 15 | 25 | 11 | 45 | 420 | 130 | 1210017 |
| ES580-02A-011G/015P-3B | 37 | 50 | 35 | 15 | 25 | 11 | 52 | 470 | 175 | 1210018 |
| Pictures and technical drawings of this product are made with reasonable care and liability is excluded for the accuracy and correctness of this data. | ||||||||||
Features of ES580/580L Series
- High reliability
- Output frequency: 0-1000 Hz (0-30000 rpm / 0-60000 rpm)
- precision control
- Intelligent LCD keyboard included in standard configuration
- Modular compact structure design
- Support SVC vector control
- Support permanent magnet synchronous motor/asynchronous motor control
- Support several kinds of field bus communication protocols
- (PROFIBUS-DP, CANopen, Profinet, EtherCAT)
- Built-in logic arithmetic function
CUMARK’s high, medium and low voltage series of intelligent frequency inverters and their related automation integrated products have a wide range of application prospects. They can be widely used in CNC machine tools and robots, marine engineering equipment, ships, rail transit equipment, Energy-saving and new energy vehicles, agricultural machinery and equipment, logistics and warehousing, electric power, coal, petrochemical, chemical, environmental protection, pharmaceuticals, non-ferrous metals, steel and other fields can help manufacturers improve equipment automation, energy conservation and efficiency, and reduce production costs, help the equipment manufacturing industry products green and intelligent upgrades and improve market competitiveness.



| Comparation | ES350 Series | ES355 Series | ES560 Series | ES580 Series | ES850 Series |
![]() | ![]() | ![]() | ![]() | ![]() | |
| Market Position | Compact AC Drive | Compact AC Drive | High Performance | High Performance | High Precision Drive |
| Power Rage | 1 phase 220v: 0.4kw~4kw; 3 phase 220v: 0.75kw~2.2kw; 3 phase 380v/440v: 0.4kw~4kw; | 1 phase 220v: 0.4kw~4kw; 3 phase 220v: 0.75kw~2.2kw; 3 phase 380v/440v: 0.4kw~4kw; | 5.5kw~560kw; 3 phase 380v | 3 phase 380v/440v: 5.5kw~560kw; 3 phase 220v: 4kw~55kw; | 3 phase 380v/440v: 5.5kw~560kw; 3 phase 690V: 15kw~1250kw |
| Keypad | LED default, LCD optional | LED default, LCD optional | LED default, LCD optional | LCD default | LCD default |
| EMC | Built in C3 filter (IEC61800-3 C3 | Built in C3 filter (IEC61800-3 C3 | Built in C3 filter (IEC61800-3 C3 ) | Built in C3 filter (IEC61800-3 C3 ) | Built in C3 filter (IEC61800-3 C3 ) |
| Control Mode | Vector | V/F control, Vector control | V/F, vector | Vector | Open loop vector, Closed loop vector |
| Digital Input | 5 ( DI1-DI5) terminals digital on/ off; 1 ( DI6) HDI,Max 50kHz | 4 terminals digital input Support PNP and NPN,among DI4 support 60Khz high speed pulse | 7 terminals Digital input/1 ( DI7) HDi,Max 50kHz | 6 ( DI1-DI6) terminals digital on/ off; 1 ( DI7) HDi,Max 50kHz | 6 ( DI1-DI6) terminals digital on/off; 1 ( DI7) HDI, Max 50kHz |
| Digital output | 1( DOl), in pulse output 0~50KHZ | 1( DOl),60Khz high speed pulse output/0~50KHZ | 1( D01);xx 1( D02) Impulse output 0~50KHZ | 1( D01);xx 1( D02) Impulse output 0~50KHZ | 1( DOl); 1( D02) Impulse output 0~50KHZ |
| Analog Input | 2 (Al2, AI3) 0~10V/0~20mA | 1 input terminal 0~10V/4~20mA | 2 ( AI2, Al3) 0~10V/0~20mA, 1 (All) 0~10V | 2 ( AI2, Al3) 0~10V/0~20mA, 1 (All) 0~10V | 2 ( AI2, Al3) 0~10V/0~20mA, 1 (All) 0~10V |
| Analog output | 1 (AO) 0~10V /0~20mA | 1 output terminal 0~10V/4~20mA | 2 (AOl, A02) 0~10V/0~20mA | 2 (AOl, A02) 0~10V/0~20mA | 2 (AOl, A02) 0~10V/0~20mA |
| Relay output | 1 Relay Output NO open, NC close, CM COM 3A/AC250V, 1A/DC30V | 1 Relay Output terminals NO/NC selection | 2 relay output R1 NO open, R1 NC close, R1 CM COM; R2 NO open, R2 NC close, R2 CM COM; 3A/AC250V, 1A/DC30V | 2 Relay Output R1 NO open, R1 NC close, R1 CM COM; R2 NO open, R2 NC close, R2 CM COM; 3A/AC250V, 1A/DC30V | 2 Relay Output R1 NO open, R1 NC close, R1 CM COM; R2 NO open,R2 NC close, R2 CM COM; 3A/AC250V, 1A/DC 30V |
| STO | / | 2 | 2 | 2 | 2 |
| Protection Class | IP20/IP40 (optional) | IP20 | IP40 (5.5kw~22kw optional); IP20(30kw~560kw); | IP40 (5.5kw~22kw optional); IP20(30kw~560kw); | IP40(5.5kw~22kw optional); IP20(30kw~560kw); |
| DC reactor | / | / | Above 15KW built in | Above 15KW built in | Above 15KW built in |
| Motor Overheat Protection | ✓ | ✓ | ✓ | ✓ | ✓ |
| PLC Logic Terminals control | ✓ | ✓ | ✓ | ✓ | ✓ |
| PG Card | / | / | / | / | ✓ |
| Certificates | CE | CE | CE | CE | CE |
| Brake Unit | ✓ | ✓ | 5.5kw~22kw built-in; 30kw~90kw optional; | 5.5kw~22kw built-in; 30kw~90kw optional; | 5.5kw~22kw built-in; 30kw~90kw optional; |
| Support Communication | RS485, RJ45, Modbus-RTU | built in modbus interface Simple CANopen | RS485, RJ45, Modbus-RTU, CANopen, Profibus-DP,EtherCAT | RS485, RJ45, Modbus-RTU, CANopen, Profibus-DP,EtherCAT | RS485, RJ45, Modbus-RTU, CANopen, Profibus-DP,EtherCAT |
| Pictures and technical drawings of this product are made with reasonable care and liability is excluded for the accuracy and correctness of this data. | |||||
| Item | Specification and Technical Data | |
| Main power | Input voltage Ul | 220V/380V/500/690V±15%;signal/three-phase power |
| Input frequency f1 | 50…60HZ ±5Hz | |
| Output voltage U2 | 0…U1 (V)(The maximum output voltage equals the input power voltage.) | |
| Output frequency f2 | 0-1000 Hz | |
| Carrier frequency | 2-8 KHz (The device can intelligently and automatically make optimal adjustment according to load characteristics and drive temperature.) | |
| Input voltage unbalance degree | Maximum: ±3% of rated inter-phase input voltage | |
| Efficiency | ~ 98% (when operating at rated power) | |
| Basic functions | Speed range | 0-1000 Hz (0-30000 rpm, 60000 rpm is optional) |
| Resolution of given speed | Digital setting: 1RPM Analog setting: 0.025% of maximum RPM | |
| Control mode | SVC control / FVC vector control | |
| Starting speed | 200% @ 0.25Hz@ SVC control 200% @0Hz@ FVC control | |
| Speed ratio | 1:200 @ SVC control 1: 3000 @ FVC control | |
| Steady-speed precision | ±0.5% @ SVC control ±0.01% @ FVC control | |
| Overload capacity | Heavy load application: 60s at 150% rated current @40°C.The time depends on the drive temperature under other conditions. General application: 60s at 120% rated current @40°C. The time depends on the drive temperature under other conditions. | |
| Torque boost | Automatic torque boost. Manual torque boost 0.1%-30% | |
| Acceleration and deceleration curves | straight-line or S-curve acceleration and deceleration mode Two acceleration time values. The acceleration and deceleration time range: 0.0s-650.00s | |
| Simple PLC function | Achieve operation of up-to-16-stages speed(via built-in PLC or control terminals) | |
| Built-in PID | Conveniently achieve the process control close-loop control system | |
| Automatic voltage regulation (AVR) | When the grid voltage changes, the device automatically maintains constant output voltage. | |
| Overvoltage and overcurrent stall control | The current and voltage are automatically limited during running to avoid jump faults due to frequent overcurrent and overvoltage | |
| Enhancements | Torque limiting and control | The torque is automatically limited operating (to avoid frequent overcurrent jumping fault due to too large torque). |
| Protection function | Output short circuit protection, input & output phase loss protection, overcurrent protection, overvoltage protection,undervoftage protection, overheat protection, overload protection, brake chopper overload protection, brake chopper short circuit protection, brake resistor overload protection | |
| Non-stop during transient interruption | Keep the frequency converter operating in a short time (by reducing feedback energy compensation voltage at the moment of power outage). The duration depends on the mechanical inertia of the load at that time. | |
| Speed tracking restart | Asynchronous motor speed tracking start can be realized ( standard) and synchronous motor speed tracking start (optional) | |
| Timing control | Timing control function. The time range and precision is 0.0-6500.0(min). | |
| Switching multiple motors | Support switching among four groups of motor parameters. | |
| Bus communication | The standard configuration uses the built-in Modbus/communication, which can be extended to Profibus-DP , CANopen bus communication. Etc. | |
| Intelligent temperature control | Full cover system temperature testing intelligent real-time IGBF chip temperature monitoring and intelligent and optimized adjustment of the carrier ancfcurrent based on drive temperature changes | |
| Type of encoders supported | Support differential encoders, collector open encoders, rotary transformer encoders, and Sin-Cos Encoders | |
| Communication linkage synchronization | Easily realize multi-motor synchronous transmission, and can freely choose to realize the linkage balance of multi-motor by current torque or power. | |
| Debug window | Visual parameter debugging, fault display and waveform monitoring can be easily realized through the PC terminal etc. | |
| I/O Input Output Interface | Command input mode | Control keyboard input, control terminal input, bus communication input, which can be switched mutually. |
| Speed reference mode | Digital giving, analog voltage (current) giving, pulse giving, bus communication giving and PID giving, which are mutually switched. | |
| Input terminal (input) | The followings are included in standard configuration : 6 (FO) / 7 (FI and above) digital input terminals, where, DI6 (FO) DI7 (FI and above)supports the maximum of 50 kHz high-speed pulse input. 2 (FO) /3 (FI and above) analog input terminals (where, at least 2 supports 0-10V voltage input or 0-20 mA or 4-20mA voltage input) The followings are extended as cards : 5 digital input terminals 2 analog input terminals, supporting input of -10V to+lOV voltage (Optional) | |
| Output terminal (output) | The followings are included in standard configuration: 1 high-speed pulse output terminal (supporting 0-50 kHZ square signal output) 1 (F0) /2 (FI and above) digital output terminals 1 (F0) /2 (FI and above) relay output terminals 1 (F0) /2 (FI and above) analog output terminals (supporting 0-10V voltage output or 0- 20mA or 4-20 mA voltage output) | |
| Pictures and technical drawings of this product are made with reasonable care and liability is excluded for the accuracy and correctness of this data. | ||